PRESCRIBED DETAILS FOR A HVAC SYSTEM: MATERIALS, FABRICATION, DESIGN, INSTALLATION, AND PERFORMANCE TESTING
MINIMUM MATERIALS SPECIFICATIONS
Coming up next are the least materials particulars prescribed to accomplish a significantly tight establishment that will last:
All Materials
Will have a base exhibition temperature evaluations per UL181 (conduits), UL181A (conclusion frameworks for unbending channels), UL181B (conclusion frameworks for adaptable pipes) or potentially UL 181BM (mastic);
Will have a fire spread rating of close to 25 and a most extreme smoke created a rating of 50 (ASTM E 84)
Processing plant Fabricated Duct Systems
All processing plant created conduit frameworks will incorporate UL 181 recorded pipes with endorsed conclusion frameworks including collars, associations and joins;
All weight delicate and heat-enacted tapes utilized in the production of unbending fiberglass channels will be UL 181A recorded;
All weight delicate tapes and mastics utilized in the production of adaptable pipes will be UL 181B (tape) or UL 181BM (mastic) recorded.
Field-Fabricated Duct Systems
Channels:
Processing plant made pipes for field-manufactured channel frameworks will be UL 181 recorded.
Mastic sealants and work:
Sealants will be UL 181BM recorded, non-lethal, and water safe;
Sealants for inside applications will finish ASTM tests C 731 (extrudability subsequent to maturing) and D 2202 (droop test on vertical surfaces);
Sealants and lattices will be evaluated for outside use;
Sealants for outside applications will breeze through ASTM tests C 731, C 732 (counterfeit enduring test), and D 2202.
Weight touchy tapes:
Weight touchy tape will be that prescribed by and meet the prerequisites of the flex duct maker;
Tape utilized for conduit board will be UL 181A recorded thus shown with a UL 181A imprint or aluminum-upheld butyl sticky tape (15 mil. least).
Drawbands:
Will be either tempered steel worm-drive hose cinches or uv-safe nylon channel ties;
Will have a base act temperature rating of 165 degrees Fahrenheit (consistent, per UL 181A-type test) and a base elasticity rating of 50 pounds;
Will be fixed as suggested by the producer with a flexible tensioning device.
PLAN, FABRICATION, AND INSTALLATION
Coming up next are plan, creation and establishment rules, that, if deliberately pursued, will give a pipe establishment that is considerably hermetically sealed:
General Issues
Conduits, plenums, and fittings ought to be developed of excited metal, channel board, or adaptable pipe. Building depressions may not be utilized as a pipe or plenum without a fixed channel board or metal liner.
The air handler box ought to be sealed shut;
Air channels ought to be effectively open for substitution, and evaporator curls ought to be effectively available for cleaning;
Conduits ought to be designed and upheld in order to counteract utilization of abundance material, anticipate separation or harm, and forestall tightening of channels beneath their appraised breadth;
Adaptable channel twists ought not to be made crosswise over sharp corners or have accidental contact with metal installations, funnels, or courses that can pack or harm the ventilation work;
Sheet metal collars and sleeves ought to be beaded to hold draw bands.
STRUCTURE OF HVAC SYSTEM
Burdens and CFM Calculation
ACCA Manual J Load Calculation or comparable required;
Figure heat misfortune and warmth gain for each room;
All out room burdens to decide framework prerequisites.
Spread Out Air Distribution System
Spread out pipe framework on the floor plan and decide register positions and pipe ways to improve room air flow and limit pipe length;
Conduit ways must record for areas and bearings of joists, rooftop hips, fire dividers, and other potential blocks;
Conduit ways must be intended to keep away from sharp turns of flex duct that will crimp the pipe.
Measure Air Distribution System
ACCA Manual D Duct Design or identical required;
Compute right cfm for each room and aggregate for structure for both supply and return;
Measure conduits as per Manual J loads, Manual D wind streams, and last design on plans;
Pick registers to streamline air circulation and pipe static weight;
Measure and find come back to upgrade wind stream per Manual D;
For return-channel barbecues, figure least return channel territory per Manual D.
Select System
ACCA Manual S Residential Equipment Selection or proportionate required. ACCA, 1515 sixteenth St., NW, Washington, DC 20036, (202)483-9370;
From Manual J burdens and Manual D cfm, decide fitting gear
Gear ought to be measured to reasonable burdens;
Gear reasonable limit ought not be over 15% bigger than the complete reasonable structure load (as indicated in Manual S).
No comments